UPS EATON 93T 20KVA IB 9106-52315 SIN BAT


  • Marca: EATON
  • Código: 37370
  • Garantía: 12 meses

Descripción

Parte: 9106-52315
https://www.eaton.com/es/es-es/skuPage.93T20KMBS.html

Eaton 93T 15-200kVA UPS technical specifications
Capacity Rated capacity/active power (kVA/kW) 100/100 120/120 160/160 200/200
Input Rated input voltage (Vac) 380/400/415
Input voltage range (Vac) 201-478
Rated input frequency (Hz) 50/60
Input frequency range (Hz) 40-72
Bypass voltage range (Vac) +/- 15% by default, +/- 20% optional
Input power factor > 0.99
Input current THDi (@ rated linear load) < 3%
Icc rating (kA) 35

Output Rated output voltage (M) 380/400/415
Rated output frequency (Hz) 50/60
Power factor 1
Output voltage regulation (steady state) ±1%
"Output voltage tolerance regulation
(dynamic)" ±5% (0-100% load variation)
Output voltage THDv (@ full linear load) < 2%
Inverter overload capacity 10 minutes, @125%

Productivity Double-conversion mode > 96%
ESS mode 99%

Parallel Parallel unit Up to 4

Battery configuration Battery type VRLA, NiCad,Lithium-ion
Battery blocks quantity (with external VRLA batteries) 32-44
Charging method BMS, ABM, or constant float charge
Connection Support common battery

Dimension W*D*H (mm) 500*850*1260 550*850*1600

Weight Net weight (kg) without switch 177 177 260 290
Net weight (kg) with switch 203 203 281 311

Cable Entry Bottom/Top Bottom

Communication Communication interface 2 mini-slots, 3 building alarms inputs, and 1 RS232&1 USB
Communication accessories "Gigabit network card; Industrial gateway card;
EMP temperature and humidity sensor; AS/400 relay/RS-232 interface card"

Others Temperature 0-50?*
Humidity 5-95%, non-condensing
Altitude < 1000 m, no derating
Noise (1m) = 65dB
Safety IEC62040-1
EMC compatibility IEC62040-2
Performance IEC62040-3
Certification TLC, CQC energy saving, and Seismic test report